2 Wires Non-Position Leak Detection Cable

2 Wires Non-Position Leak Detection Cable
Main Specification:
Cable diameter: 0.17″(4.5mm)nominal
Sensing Wires: 2*30 AWG with jacket of conductive fluoropolymer
Carrier: Fluoropolymer
Cable weight: (50 ft/15m length) 500g
Cable color: High-visibility yellow

Breaking strength: Cable only:158 Ib(72KG).
Including connectors:70 LB(32kg)

Cut-through force: >48.4 LB with 0.005(>22kg with with 0.13mm) in blade,
cross head speed 0.2in/min
Abrasion resistance: >65 cycles per UL719
Maximum continuous operating temperature: 70degree
Leak size to alarm(tap water): 2in(50mm)maximum at any point along sensing cable,p to 5000 ft maximum system length

Drying time: Cable dries and resets within 15 seconds after removal from standing water.
Standard cleaning method: Wipe with clean damp cloth

Advanced technology for 2 wires Non-Position Leak Detection Cable:
The conductive-polymer technology and fluoropolymer construction make

the cable mechanically strong and resistant to corrosion and abrasion.

The cable is constructed of two sensing wires,embedded in a fluoropolymer carrer rod.
The alarm module constantly monitors the sensing cable for continuity
The rugged cable construction exposes no metal,
and enables the cable to be reused even in corrosive environments.