Fuel Leak Detection Wire
Product Name: Fuel Leak Detection Wire
Model : P-LFP6000
Product Features:
Cable Diameter : 0.52 in (13mm) nominal
Cable Diameter: 0.32 in (8mm) nominal
Connector
Cable weight: 7.3 kg/100 m nominal (4.81 lb/100 ft nominal)
Fluoropolymer braid Color – red white and black
Operating temperature: –20°C to 60°C (–4°F to 140°F)
Range
Pull force limit: Not to exceed 22.7 kg (50 lb)
Bend radius: 50 mm (2 in) minimum
Pressure: Loads greater than 9 kg (20 lb) per linear inch at 20°C (68°F) may immediately trigger an alarm
Nonresettable: Must be replaced after exposure to hydrocarbon liquids
Technical information for this Fuel Leak Detection Wire
Chemical resistance
Cable functions normally: Sulfuric acid (10%)
after exposure in Hydrochloric acid (10%)
accordance with ASTM D Nitric acid (10%)
543 at 23°C (73°F) for Sodium hydroxide (10%)
Sensing cable Less than 10μA leakage when immersed in salt water for 90 days
Connector system Less than 10 μA leakage when immersed in water at 10 psig for 24 hours
Response time
Represented materials Typical response time at
detected 20°C (68°F)
Gasoline 3 minutes
#1 diesel fuel 30 minutes
#2 diesel fuel 60 minutes
JP5 jet fuel 30 minutes
JP8 jet fuel 20 minutes
Jet-A jet fuel 20 minutes
Xylene 10 minutes